Model | NE-48D100-NP | |
Electrical Characteristics | Nominal Voltage | 48V |
Nominal Capacity | 100Ah (±3%) | |
Energy | 4800Wh | |
Internal Resistance | ≤100mOhm (≤20mOhm without BMS) | |
Cycle Life | ≥4000 cycles @85% DOD, 35℃ | |
Design Life | ≥20 years @25℃ | |
Self-Discharge (90 days) | ≤3%@25℃ | |
Efficiency of Charge | ≥98% | |
Efficiency of Discharge | ≥100% @ 0.2C;≥96% @ 1C | |
Charge | Charge Voltage | 54.0V±0.1V |
Charge Mode | Max. 1C to 54.0V, then 54.0V charge current to 0.02C (CC/CV) | |
Max. Charge Current | 100A | |
Charge Cut-off Voltage | 54V±0.2V | |
Discharge | Max. Continuous Discharge Current | 100A |
Discharge Cut-off Voltage | 42.5V±0.2V | |
Environmental | Charge Temperature Range | 0℃~60℃ |
Discharge Temperature Range | -20℃~60℃ | |
Optimum Operation Temperature | 5℃~45℃ | |
Storage Temperature | 0℃~35℃ ≤85% relative Humidity | |
Water Dust Resistance | IP21 | |
Mechanical | Case | Iron (Insulation painting) |
Dimensions(L*W*H) mm | 442*410*157 (±1) mm | |
Weight | 41±1kg | |
Energy Density | 114Wh/kg | |
Others | Protocol | RS485 (2 Nos) / RS232 |
SOC Light | 4 * LED | |
Parallel | Up to 15pcs | |
Cell voltage detection panel | Yes | |
Automatic Fire Suppression System | Yes |